Application Guide
Chiller Plant Design
51.5F Return Water To Chiller Two 400 Ton Chillers Each At 300 Tons (Balanced L...
137 downloads
1138 Views
3MB Size
Report
This content was uploaded by our users and we assume good faith they have the permission to share this book. If you own the copyright to this book and it is wrongfully on our website, we offer a simple DMCA procedure to remove your content from our site. Start by pressing the button below!
Report copyright / DMCA form
Application Guide
Chiller Plant Design
51.5F Return Water To Chiller Two 400 Ton Chillers Each At 300 Tons (Balanced Load)
Chiller 1- On Two Primary Pumps Each At 960 gpm
Building Load 600 Tons (50% Load)
54F
51.5F 480 gpm Flow Through Decoupler
44F
Flow
Chiller 2- On 44F
Chiller 3- Off
Secondary Pump 1440 gpm
Elevation Difference
Column Height When Pump Is Off
© 2002 McQuay International
AG 31-003-1
Table of Contents Introduction ................................................................................................................. 4 Using This Guide............................................................................................................................... 4
Basic System ............................................................................................................... 4 Chiller Basics..................................................................................................................................... 4 Piping Basics ..................................................................................................................................... 7 Pumping Basics ............................................................................................................................... 11 Cooling Tower Basics...................................................................................................................... 15 Load Basics ..................................................................................................................................... 20 Control Valve Basics ....................................................................................................................... 20 Loop Control Basics ........................................................................................................................ 23 Piping Diversity............................................................................................................................... 24
Water Temperatures and Ranges ............................................................................... 25 Supply Air Temperature................................................................................................................... 25 Chilled Water Temperature Range................................................................................................... 26 Condenser Water Temperature Range.............................................................................................. 26 Temperature Range Trends .............................................................................................................. 27
Air and Evaporatively Cooled Chillers ..................................................................... 28 Air-Cooled Chillers ......................................................................................................................... 28 Evaporatively Cooled Chillers......................................................................................................... 30
Dual Compressor and VFD Chillers ......................................................................... 31 Dual Compressor Chillers................................................................................................................ 31 VFD Chillers ................................................................................................................................... 31 System Design Changes................................................................................................................... 32
Mechanical Room Safety .......................................................................................... 34 Standard 34...................................................................................................................................... 34 Standard 15...................................................................................................................................... 34
Single Chiller System................................................................................................ 38 Basic Operation ............................................................................................................................... 38 Basic Components ........................................................................................................................... 38 Single Chiller Sequence of Operation.............................................................................................. 39
Parallel Chiller System.............................................................................................. 41 Basic Operation ............................................................................................................................... 41 Basic Components ........................................................................................................................... 41 Parallel Chiller Sequence of Operation ........................................................................................... 42
Series Chillers ........................................................................................................... 44 Basic Operation ............................................................................................................................... 44 Basic Components ........................................................................................................................... 44 Series Chillers Sequence of Operation ............................................................................................ 46 Series Counterflow Chillers............................................................................................................. 47 Using VFD Chillers in Series Arrangements ................................................................................... 49 System Comparison ......................................................................................................................... 49
Primary/Secondary Systems ...................................................................................... 51
2
Application Guide AG 31-003-1
Basic Operation ............................................................................................................................... 51 Basic Components ........................................................................................................................... 51 Very Large Chiller Plants................................................................................................................. 58 Primary/Secondary Sequence of Operation ..................................................................................... 58
Water-Side Free Cooling ........................................................................................... 61 Direct Waterside Free Cooling......................................................................................................... 61 Parallel Waterside Free Cooling ...................................................................................................... 61 Series Waterside Free Cooling......................................................................................................... 62 Waterside Free Cooling Design Approach ....................................................................................... 63 Cooling Tower Sizing ...................................................................................................................... 63 Waterside Free Cooling Sequence of Operation .............................................................................. 64 Economizers and Energy Efficiency ................................................................................................ 65
Hybrid Plants............................................................................................................. 66 Heat Recovery and Templifiers™ ............................................................................. 67 General............................................................................................................................................. 67 Load Profiles.................................................................................................................................... 67 Heat Recovery Chillers .................................................................................................................... 67 Templifiers™ ................................................................................................................................... 71 ASHRAE Standard 90.1 .................................................................................................................. 73
Variable Primary Flow Design .................................................................................. 75 Basic Operation ............................................................................................................................... 75 Basic Components ........................................................................................................................... 75 Variable Primary Flow Sequence of Operation................................................................................ 76 Training and Commissioning ........................................................................................................... 78
Low Delta T Syndrome ............................................................................................. 80 Low Delta T Example ...................................................................................................................... 80 Low Delta T Syndrome Causes and Solutions ................................................................................. 82 Other Solutions ................................................................................................................................ 84
Process Applications ................................................................................................. 86 Process Load Profiles ...................................................................................................................... 86 Condenser Relief.............................................................................................................................. 87 Winter Design .................................................................................................................................. 87 Chilled Water Volume ...................................................................................................................... 87 Temperatures and Ranges ................................................................................................................ 88
Minimum Chilled Water Volume .............................................................................. 89 Estimating System Volume .............................................................................................................. 89 Evaluating System Volume .............................................................................................................. 89
Conclusions ............................................................................................................... 92 References ................................................................................................................. 93 The information contained within this document represents the opinions and suggestions of McQuay International. Equipment, the application of the equipment, and the system suggestions are offered by McQuay International as suggestions only, and McQuay International does not assume responsibility for the performance of any system as a result of these suggestions. Final responsibility for the system design and performance lies with the system engineer.
Application Guide AG 31-003-1
3
Introduction Using chilled water to cool a building or process is efficient and flexible. A two-inch Schedule 40 pipe of chilled water can supply as much comfort cooling as 42" diameter round air duct. The use of chillers allows the design engineer to produce chilled water in a central building location or even on the roof and distribute the water economically and without the use of large duct shafts. Chilled water also provides accurate temperature control that is especially useful for variable air volume (VAV) applications. The purpose of this manual is to discuss various piping and control strategies commonly used with chilled water systems including variable flow pumping systems.
Using This Guide This Guide initially discusses the components used in a chilled water system. It then reviews various chiller plant designs explaining their operation, strengths and weaknesses. Where appropriate, sequence of operations are provided. Each project is unique so these sequences are just guidelines. In addition, many sections reference ASHRAE Standard 90.1-2001. The ASHRAE section numbers are provided in parentheses to direct the reader. The sections referenced in this Guide are by no means complete. It is recommended that the reader have access to a copy of Standard 90.1 as well as the Users Manual. The Standard and manual can be purchased online at WWW.ASHRAE.org.
Basic System Figure 1 shows a basic chiller loop with a water-cooled chiller. The system consists of a chiller, cooling tower, building cooling load, chilled water and condensing water pumps and piping. This section will review each of the components. Figure 1 - Single Chiller Loop
Chiller Basics The chiller can be water-cooled, air-cooled or evaporatively cooled. The compressor types typically are reciprocating, scroll, screw or centrifugal. The evaporator can be remote from the condensing section on air-cooled units. This has the advantage of allowing the Building Load chilled water loop to remain inside the building envelope when using Condenser an outdoor chiller. In applications Water Loop where freezing conditions can be expected, keeping the chilled water Cooling Tower loop inside the building avoids the Chilled Water Pump need for some form of antifreeze.
Condenser Water Pump
4
Chiller
Chilled Water Loop
There can be multiple chillers in a chilled water plant. The details of various multiple chiller plant designs will be discussed in future sections.
Application Guide AG 31-003-1
The chilled water flows through the evaporator of the chiller. The evaporator is a heat exchanger where the chilled water gives up its sensible heat (the water temperature drops) and transfers the heat to the refrigerant as latent energy (the refrigerant evaporates or boils).
Flow and Capacity Calculations For air conditioning applications, the common design conditions are 44°F supply water temperature and 2.4 gpm/ton. The temperature change in the fluid for either the condenser or the evaporator can be described using the following formula: Q = W x C x ∆T Where Q = Quantity of heat exchanged (Btu/hr) W = flow rate of fluid (USgpm) C = specific heat of fluid (Btu/lb· °F) ∆T = temperature change of fluid (°F ) Assuming the fluid is water, the formula takes the more common form of: Load (Btu/hr) = Flow (USgpm) x (°Fin – °Fout) x 500 Or Load (tons) = Flow (USgpm) x (°Fin – °Fout)/24 Using this equation and the above design conditions, the temperature change in the evaporator is found to be 10°F. The water temperature entering the evaporator is then 54°F. Most air conditioning design conditions are based on 75°F and 50% relative humidity (RH) in the occupied space. The dewpoint for air at this condition is 55.08°F. Most HVAC designs are based on cooling the air to this dewpoint to maintain the proper RH in the space. Using a 10°F approach at the cooling coil means the supply chilled water needs to be around 44°F or 45°F. The designer is not tied to these typical design conditions. In fact, more energy efficient solutions can be found by modifying the design conditions, as the project requires. Changing the chilled water flow rate affects a specific chiller's performance. Too low a flow rate lowers the chiller efficiency and ultimately leads to laminar flow. The minimum flow rate is typically around 3 fps (feet per second). Too high a flow rate leads to vibration, noise and tube erosion. The maximum flow rate is typically around 12 fps. The chilled water flow rate should be maintained between these limits of 3 to 12 fps. The condenser water flows through the condenser of the chiller. The condenser is also a heat exchanger. In this case the heat absorbed from the building, plus the work of compression, leaves the refrigerant (condensing the refrigerant) and enters the condenser water (raising its temperature). The condenser has the same limitations to flow change as the evaporator.
Chillers and Energy Efficiency Chillers are often the single largest electricity users in a building. A 1000 ton chiller has a motor rated at 700 hp. Improving the chiller performance has immediate benefit to the building operating cost. Chiller full load efficiency ratings are usually given in the form of kW/ton, COP (Coefficient of Performance = kWcooling / kWinput) or EER (Energy Efficiency Ratio = Tons X 12/ kWinput). Full load performance is either the default ARI conditions or the designer specified conditions. It is important to be specific about operating conditions since chiller performance varies significantly at different operating conditions.
Application Guide AG 31-003-1
5
Chiller part load performance can be given at designer-specified conditions or the NPLV (NonStandard Part Load Value) can be used. The definition of NPLV is spelled out in ARI 550/590-98, Test Standard for Chillers. For further information refer to McQuay Application Guide AG 31-002, Centrifugal Chiller Fundamentals. ☺Tip: To convert from COP to kW/ton; COP = 3.516/(kW/ton) To calculate EER = Tons x 12/(total kW input) 1
Figure 2 - ASHRAE Std 90.1 Chiller Performance Table
Water Chilling Packages – Minimum Efficiency Requirements Equipment Type Air Cooled, with Condenser, Electrically Operated Air Cooled, without Condenser, Electrically Operated Water Cooled, Electrically Operated, Positive Displacement (Reciprocating) Water Cooled, Electrically Operated, Positive Displacement (Rotary Screw and Scroll)
Size Category 150 tons All Capacities All Capacities 150 tons and 300 tons Water Cooled, Electrically Operated, Centrifugal
l50 tons and 300 tons
Air-Cooled Absorption Single Effect Water-Cooled Absorption Single Effect Absorption Double Effect, IndirectFired Absorption Double Effect, Direct-Fired
All Capacities All Capacities All Capacities All Capacities
Subcategory or Rating Condition
Minimum Efficient
Test Procedure
2.80 COP 3.05 IPLV
ARI 550/590
3.10 COP 3.45 IPLV 4.20 COP 5.05 IPLV 4.45 COP 5.20 IPLV
4.90 COP 5.60 IPLV 5.50 COP 6.15 IPLV 5.00 COP 5.25 IPLV 5.55 COP 5.90 IPLV 6.10 COP 6.40 IPLV 0.60 COP 0.70 COP
ARI 550/590 ARI 550/590
ARI 5 50/590
ARI 560
1.00 COP 1.05 IPLV 1.00 COP 1.00 IPLV
a The chiller equipment requirements do not apply for chillers used in low-temperature applications where the design leaving fluid temperature is 60
0.22-0.28 0.22-0.28
Mean Rating Temp °F
Nominal Pipe or Tube Size (in)